Summary Of Main Steps; Boot Code Upgrade (*) - GE F650 User Manual

Grid solutions digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

5.1 FIRMWARE UPGRADE VERSIONS BELOW 7.00.
12. When the file transfer is finished, a message is displayed indicating that it is necessary to wait before resetting the
unit, in order to start working with the new firmware version in the relay (figure below).
13. When the whole process has finished a message is displayed asking to switch the F650 on and off (figure below).
14. Click Ok (Aceptar). At this point, the firmware upgrade is finished and the relay can be powered OFF and ON to check
that the firmware has been upgraded properly.
15. User settings and logic files downloading
When upgrading the firmware the entire settings and relay configuration are reset to factory default values. Then the
User is committed to download the settings, configuration and logic files to the relay in order to get it fully operative.
Calibration settings and configuration must be reloaded to the relay the relay.
To recover and download the different files to the relay go to Enervista 650 Setup and at the top menu bar choose:
Communication > Calibration > Set Calibration Files: to restore calibration settings, if necessary.
File > Config File (*.650) Converter: to convert the setting and configuration file *.650 for the relay (if it was in a
previous version format).
File > Send Info to Relay: to send the new settings and configuration file to the unit.

5.1.4 Summary of main steps

5.1.4.1 Boot code upgrade (*)

1.
Install the proper version of the EnerVista 650 Setup software.
5-20
Figure 5-11: Firmware file selection
F650 DIGITAL BAY CONTROLLER
CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE
GEK-113000-AF