GE F650 User Manual page 273

Grid solutions digital bay controller
Hide thumbs Also See for F650:
Table of Contents

Advertisement

APPENDIX D:
Operation time
Deviation time to instantaneous
Snapshot event generation
Setpoint > Protection Elements > Sensitive Ground Current > Sensitive Ground Directional >
Sensitive Ground Directional 1 > Sensitive Ground Directional 2 > Sensitive Ground Directional 3
Setting Description
Function permission
Maximum Torque Angle
Operation Direction
Block logic type
Polarization voltage threshold
Snapshot event generation
Setpoint > Protection Elements > Negative Sequence Current > Negative Sequence TOC >
Negative Sequence TOC 1 > Negative Sequence TOC 2 > Negative Sequence TOC 3
Setting Description
Function permission
Pickup level
Curve shape
Time Dial
Reset type
Snapshot Event generation
Setpoint > Protection Elements > Voltage Elements > Phase UV >
Phase UV 1 > Phase UV 2 > Phase UV 3
Setting Description
Function permission
Input mode
Pickup Level
Curve shape
Time Dial
Minimum Voltage Threshold
Operation logic
Supervision by breaker status
Snapshot Event generation
Setpoint > Protection Elements > Voltage Elements > Phase OV >
Phase OV 1 > Phase OV 2 > Phase OV 3
Setting Description
GEK-113000-AF
Delay
0.00
Time to inst
0.00
Snapshot Events
ENABLED
Name
Default Value
Function
DISABLED
MTA
-45
Direction
FORWARD
Block Logic
PERMISSION
Pol V Threshold
10
Snapshot Events
ENABLED
Name
Default Value
Function
DISABLED
Pickup Level
1.00
Curve
IEEE Ext Inv
TD Multiplier
1.00
Reset
INSTANTANEOUS
Snapshot Events
ENABLED
Name
Default Value
Function
DISABLED
Mode
PHASE-PHASE
Pickup Level
10
Curve
DEFINITE TIME
Delay
10.00
Minimum Voltage
5
Logic
ANY PHASE
Supervised by 52
DISABLED
Snapshot Events
ENABLED
Name
Default Value
F650 DIGITAL BAY CONTROLLER
D.1 FACTORY DEFAULT SETTINGS
0.01
[0.00 : 900.00]
s
0.01
[0.00 : 900.00]
s
N/A
[DISABLED – ENABLED]
Step Range
N/A
[DISABLED – ENABLED]
1
[-90 : +90]
Deg
N/A
[FORWARD – REVERSE]
N/A
[BLOCK – PERMISSION]
1 V
[0 : 300]
N/A
[DISABLED – ENABLED]
Step Range
N/A
[DISABLED – ENABLED]
0.01
[0.05 : 160.00]
A
N/A
[See list of curves]
0.01
[0.00 : 900.00]
s
N/A
[INSTANTANEOUS – LINEAR]
N/A
[DISABLED – ENABLED]
Step Range
N/A
[DISABLED – ENABLED]
[PHASE-PHASE, PHASE-
N/A
GROUND]
1 V
[3 : 300]
[DEFINITE TIME – INVERSE
N/A
TIME]
0.01
[0.00 : 900.00]
s
1 V
[0 : 300]
[ANY PHASE – TWO PHASES
N/A
– ALL PHASES]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
Step Range
User
Value
User
Value
User
Value
User
Value
d-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents