CHAPTER 5: BOOTCODE AND FIRMWARE UPGRADE
through cable for hub or switch).
3.
Set the appropriate IP address in the relay.
4.
Set the appropriate IP address in the PC.
5.
In the EnerVista 650 Setup software, select Communication > Upgrade Relay.
6.
Select the appropriate file (DCL000CAXXX.SDF) for the upgrade.
7.
Enter the IP address, serial number, and unit identifier of the relay as prompted.
8.
Click Upgrade File to initiate the upgrade process.
9.
Reboot the relay as required by the upgrade program to complete the upgrade process.
10. All setting and configuration are now set to the factory default.
11. Send new settings and configuration files to the relay if needed.
See chapter 13 F650 trouble shooting guide, if there is any problem during the upgrading
process.
GEK-113000-AF