6.13 DIRECTIONAL ELEMENTS (67P, 67N, 67G, 67SG)
Pol V Threshold
Configure one of the outputs to be activated only by unit 50SG.
Apply the following tests:
Elements
50SG/67SG
6-16
10 V
Phase under test
Channel
Magnitude
Mod
Arg
ISG
2 A
0º
F650 DIGITAL BAY CONTROLLER
Polarization Phase
Channel
Magnitude
Mod
Arg
VI
60 V
0º
60 V
180º
VII
0 V
0º
VIII
0 V
0º
CHAPTER 6: COMMISSIONING
Element trip
NO
YES