6.26.3 Power running stall continuous trip detection time

f452 : Power running stall continuous trip detection time
• Function
A function for preventing lifting gear from failing accidentally. If the stall prevention function is activated in
succession, the inverter judges that the motor has stalled and trips.
[Parameter setting]
Title
f452 Power running stall continuous trip detection time
f441
f601
6
1) In case of overcurrent stall
ot2 trip is occurred if the output current reached the stall prevention level (f601) or more, and this situation
maintain in f452 during power running.
Function
Power running torque limit 1 level
Stall prevention level 1
Output frequency [Hz]
Output current [%]

Adjustment range
0.00-10.00 (s)
0-249%,
250:Disabled
10-199,
200 (disabled)
"2" trip
Time [s]
Time [s]
less than


F-92
E6581926
Default setting
0.00
250
150