Adapt fieldbus configuration
6.4 Communication via PROFIBUS
6.4.5
Select telegram
PROFIdrive telegrams
If you have not activated the function "Basic positioner" in the inverter, the following tele-
grams will be available:
p0922 =
The following values apply if you have enabled the "Basic positioner" function in the inverter:
A more detailed depiction of the individual telegrams can be found in Section Cyclic
communication (Page 88).
Selecting a telegram
Procedure
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.
112
1:
Standard telegram 1, PZD-2/2 (factory setting)
2:
Standard telegram 2, PZD-4/4
3:
Standard telegram 3, PZD-5/9
4:
Standard telegram 4, PZD-6/14
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352:
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
999:
Extend telegrams and change signal interconnection (Page 103)
7:
Standard telegram 7, PZD-2/2
9:
Standard telegram 9, PZD-10/5
110:
SIEMENS telegram 110, PZD-12/7
111:
SIEMENS telegram 111, PZD-12/12
999:
Factory setting. See also Extend telegrams and change signal intercon-
nection (Page 103)
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB