Performance Ratings Power Module - Siemens SINAMICS G120D Operating Instructions Manual

With control units cu250d-2
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

11.2

Performance ratings Power Module

SINAMICS G120 D performance ratings
Table 11- 2
Feature
Line voltage & power
ranges
Line specification
Output voltage
Input frequency
Output frequency
cos φ
Converter efficiency
Overload capability (HO)
Inrush current
Pulse frequency
Electromagnetic compat-
ibility
Protection level
Temperature range
Storage temperature
Humidity
Operational altitude
Protection features
Standards
CE mark
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Power Module performance ratings
Specification
3 AC 380 V ... 500 V ± 10 %
High Overload: 0.75 kW ... 7.5 kW (1.0 hp ... 10.0 hp)
Relative short-circuit voltage of a transformer u
The specification only refers to the total instantaneous regenerative feed-
back, however not to the total connected power of all of the power mod-
ules connected to the same transformer.
Further information: FAQ
(http://support.automation.siemens.com/WW/view/en/34189181).
3 AC 0 V ... line volage × 0.87 (max.)
47 Hz ... 63 Hz
0 Hz ... 240 Hz
1.05
95 % ... 97 %
2 x Nominal output current for 3 seconds followed by 1.5 x Nominal output
current for 57 seconds every 300 seconds
Less than rated input current
4 kHz (standard); 4 kHz ... 16 kHz (in 2 kHz steps)
Internal Class A filters according to EN 55011
IP65 (when Power Module and Control Unit is fully assembled)
Standard CU: -10 °C ... +40 °C (14 °F ... 104 °F) - High Overload (HO)
Fail-Safe CU: 0 °C ... +40 °C (32 °F ... 104 °F) - High Overload (HO)
-40 °C ... +70 °C (-40 °F ... 158 °F)
< 95% RH - non-condensing
Up to 1000 m (3280 ft) above sea level without derating
Undervoltage, Overvoltage, Overload, Ground faults, Short circuit, Stall
prevention, Motor blocking protection, Motor overtemperature, Power
Module overtemperature, Parameter interlock
UL, cUL, CE, C-tick
Conformity with EC Low Voltage Directive 73/23/EEC and filtered ver-
sions also Electromagnetic Compatibility Directive 89/336/EEC
11.2 Performance ratings Power Module
≤ 1%