Advertisement

5.2.1

Which motor fits the converter?

Ratio of the motor and inverter rated currents
The rated current of the motor must be in the range 13% to 100% of the rated converter
current.
Example: With an inverter with a rated current of 10.2 A, you can operate motors whose
rated currents are within the range of 1.3 A ... 10.2 A.
Figure 5-1
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
The rated currents of inverter and motor match
Commissioning
5.2 Preparing for commissioning
61