Siemens SINAMICS G120D Operating Instructions Manual page 327

With control units cu250d-2
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Extended settings for faults
Parameter
You can change the fault response of the motor for up to 20 different fault codes:
p2100
p2101
You can change the acknowledgment type for up to 20 different fault codes:
p2126
p2127
You can change up to 20 different faults into an alarm or suppress faults:
p2118
p2119
You will find details in function diagram 8075 and in the parameter description of the List
Manual.
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Description
Setting the fault number for fault response
Selection of the faults for which the fault response applies
Setting, fault response
Setting the fault response for the selected fault
Setting the fault number for the acknowledgment mode
Selection of the faults for which the acknowledgment type should be changed
Setting, acknowledgment mode
Setting the acknowledgment type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgment after removing the fault cause
Setting the message number for the message type
Selection of the message for which the message type should be changed
Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message
Alarms, faults and system messages
10.2 Faults