Advanced commissioning
7.9 Safe Torque Off (STO) safety function
Description
The forced checking procedure (test stop) of the basic functions is an inverter self test. The
inverter checks its circuits to switch off the torque. If you are using the Safe Brake Relay, for
a forced checking procedure, the inverter also checks the circuits of this component.
You start the forced checking procedure each time that the STO function is selected.
Using a timer block, the inverter monitors as to whether the forced checking procedure is
regularly performed.
Figure 7-65
Parameter
p9659
r9660
r9773.31
7.9.3.7

Activate settings and check digital inputs

Activate settings
Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER
To activate the settings for the safety functions, proceed as follows:
1. Press the "Copy parameters" button, to create a redundant image of your inverter
settings.
2. Press the "Activate settings" button.
3. If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
264
Starting and monitoring the forced checking procedure (test stop)
Description
Forced dormant error detection timer (Factory setting: 8 h)
Monitoring time for the forced dormant error detection.
Forced dormant error detection remaining time
Displays the remaining time until the forced dormant error detection and testing the
safety switch-off signal paths.
1 signal: Forced dormant error detection is required
Signals for the higher-level control system.
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB