Corrective maintenance
9.2 Firmware upgrade and downgrade
9.2.3

Correcting a failed firmware upgrade or downgrade

How does the inverter report a failed upgrade or downgrade?
The inverter signals a failed firmware upgrade or
downgrade with a quickly flashing RDY LED and a
lit up BF LED.
Correcting a failed upgrade or downgrade
To correct a failed firmware upgrade or downgrade you can check the following:
● Does the firmware version fulfill the requirements of your inverter?
– For an upgrade at least V4.5.
– For a downgrade at least V4.6.
● Have you inserted the card properly?
● Does the card contain the correct firmware?
● Repeat the appropriate procedure.