Siemens SINAMICS G120D Operating Instructions Manual page 324

With control units cu250d-2
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Alarms, faults and system messages
10.2 Faults
The fault buffer can accept up to eight actual faults. The next to last fault is overwritten if an
additional fault occurs after the eighth fault.
Figure 10-7
Acknowledgement
You have multiple options to acknowledge a fault, e.g.:
● PROFIdrive control word 1, bit 7 (r2090.7)
● Acknowledge via the operator panel
● Switch-off the inverter power supply and switch-on again.
Faults detected during the inverter-internal monitoring of hardware and firmware can be
acknowledged only by switching the supply voltage off and on again. The list of faults in the
List Manual contains a note on this limited acknowledgment possibility.
Emptying the fault buffer: Fault history
The fault history can contain up to 56 faults.
The acknowledgment has no effect as long as none of the causes for the faults in the buffer
have been removed. If at least one of the faults in the fault buffer has been removed (the
cause of the fault has been removed) and you acknowledge the faults, then the following
happens:
1. The inverter accepts all faults from the fault buffer in the first eight memory locations of
the fault history (indexes 8 ... 15).
2. The inverter deletes the faults that have been removed from the fault buffer.
3. The inverter writes the time of acknowledgment of the faults that have been removed into
parameters r2136 and r2109 (fault time removed).
324
Complete fault buffer
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents