Motor Temperature Monitoring Using A Temperature Sensor - Siemens SINAMICS G120D Operating Instructions Manual

With control units cu250d-2
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

7.7.2

Motor temperature monitoring using a temperature sensor

You can use one of the following sensors to protect the motor against overtemperature:
● Temperature switch (e. g. bi-metal switch)
● PTC sensor
● KTY 84 sensor
Connect the motor's temperature sensor through the motor output cable on the Power
Module.
Figure 7-49
Danger to life when live parts are touched in the motor terminal box
The temperature sensor and motor holding brake connections are at DC link negative
potential. Touching these connections can result in death or severe injury.
• Keep the motor terminal box closed whenever the mains is applied to the converter.
• Before touching the connections switch off the power supply and wait until the discharge
• Insulate the cables that are not used.
NOTICE
Device damage by earthing the motor cable
The temperature sensor and motor holding brake connections are at DC link negative
potential. Earthing these connections will damage the device.
• Use appropriate insulation on the cables.
• Insulate cables that are not used.
• Do not earth cables that are not used.
Temperature switch
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Connection of the motor's temperature sensor to the converter
DANGER
time specified on the warning labels has elapsed.
The converter interprets a resistance ≥ 100 Ω as being an opened temperature
switch and responds according to the setting for p0610.
Advanced commissioning
7.7 Protection functions
229

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents