Advanced commissioning
7.6 Basic positioner and position control
7.6.7.4

Set reference point

Description
Position the load, e.g. using the "jog" function, at the reference position in the machine.
Figure 7-40
Activate 'set home position'
Precondition
You have selected the "Homing" screen.
Procedure
To activate 'set home position', proceed as follows:
1. Interconnect this bit with the corresponding signal of your machine.
If the axis is stationary, with the signal change 0 → 1, the inverter sets its actual position
value to the reference point coordinate.
For this function, all of the other signals are of no significance.
198
Set reference point
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB