Function Block Fb283; Extend Telegrams And Change Signal Interconnection - Siemens SINAMICS G120D Operating Instructions Manual

With control units cu250d-2
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

6.2.1.10

Function block FB283

Overview
The function block FB283 is an interface block that connects an inverter with basic positioner
to a SIMATIC S7 controller via PROFIBUS/PROFINET.
The block FB283 transfers all of the required process data to and from the drive. It is suitable
for both controlling the basic positioner and for a pure speed-controlled drive.
The FB283 additionally provides the following functions:
● Reading and writing parameters in the inverter.
● Reading out the fault buffer of the inverter.
● Transferring up to 16 traversing blocks when a function is initiated.
● Reading or writing a maximum of any 10 parameters with one job, e.g. for product
adaptation.
A configuration example and a description of the FB283 can be found on the Internet: FB283
(http://support.automation.siemens.com/WW/view/en/25166781).
6.2.1.11

Extend telegrams and change signal interconnection

Following selection of a telegram, the inverter interconnects the corresponding signals with
the fieldbus interface. The inverter protects this interconnection against changes.
Extend telegram
If you want to extend a telegram, you have to do the following:
Table 6- 16
Parameter
p0922 = 999
p2079
Now you can extend the telegram by interconnecting the PZD send words and PZD receive words
with signals of your choice.
For further information refer to the function block diagrams 2468 and 2470 of the List
Manual.
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Procedure
Description
PROFIdrive telegram selection
999:
Free telegram configuration with BICO
PROFIdrive PZD telegram selection extended
Set the suitable telegram:
7:
Standard telegram 7, PZD-2/2
9:
Standard telegram 9, PZD-10/5
110:
SIEMENS telegram 110, PZD-12/7
111:
SIEMENS telegram 111, PZD-12/12
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Adapt fieldbus configuration
103

Hide quick links:

Advertisement

Table of Contents
loading