Powering On the AT-SBxPWRSYS1 DC System Power Supply

SwitchBlade x3106 Chassis Switch and AT-SBx31CFC960 Card Installation Guide
This section contains instructions on how to power on the AT-
SBxPWRSYS1 DC System Power Supply. For installation instructions,
refer to "Installing the AT-SBxPWRSYS1 DC System Power Supply" on
page 118.
The power supply unit has a ground connection and positive and negative
DC terminals. You may install the ground and power lead wires using the
terminal lugs that come with the unit. You may also use bare wire
installation. The wire requirements are slightly different for terminal
installation versus bare wire installation. Here are the wire requirements if
you are using the terminals that come with the power supply:
Two 8 AWG stranded power wires (not provided)
One 10 AWG stranded grounding wire (not provided)
Here are the wire requirements for bare wire installation:
Two 8 AWG solid or stranded power wires (not provided)
One 10 AWG solid or stranded grounding wire (not provided)
Here is a list of the required tools:
Crimping tool (not provided)
8 mm wrench (not provided)
#1, #2, and #3 Phillips-head screwdrivers (not provided)
#3 Phillips-head 30 to 40 inch-lbs Phillips-head torque screwdriver
(optional - not provided)
Here are the procedures for powering on the AT-SBxPWRSYS1 DC
Power Supply:
page 181
page 186
page 193
The components of the power supply are identified in Figure 117 on page
179