+48 VDC Positive
Terminal
Figure 71. DC Terminal Block on the DC AT-PWR250 Power Supply
4. With a 14-gauge wire-stripping tool, strip the three wires in the tray
cable coming from the DC input power source to 8mm ± 1mm (0.31 in.,
± 0.039 in.), as shown in Figure 72 on page 104.
Warning
Do not strip more than the recommended amount of wire. Stripping
more than the recommended amount can create a safety hazard by
leaving exposed wire on the terminal block after installation.  E10
8mm ±1mm
(0.31in. ±0.039in.)
5. Insert the power supply ground wire into the middle connector of the
DC terminal and tighten the connection with a flathead screwdriver, as
shown in Figure 73 on page 105.
40-60VDC
DC OUT
6A
FAULT
+
-
ON
OFF
Ground
-48 VDC Negative
Terminal
Module

Figure 72. Stripped Wire