Siemens Vector Control Operating Instructions Manual page 345

Frequency converter (ac-ac) compact type
Hide thumbs Also See for Vector Control:
Table of Contents

Advertisement

Available languages

Available languages

05.2006
P060 = 5
P068 = ?
P071 = ?
P095 = ?
P095 =
P095=11
P095=2
10,12,13
P097 = ?
P100 = ?
P095=2
P097>0
P101 = ?
P102 = ?
P103 = ?
IEC
NEMA
Siemens AG
6SE7087-2JD60
SIMOVERT MASTERDRIVES
Select "Drive setting" menu
Output filter
0 = without output filter
1 = with sinusoidal output filter
2 = with dv/dt output filter
Input unit line voltage in V
AC units: r.m.s. alternating voltage
DC units: DC link voltage
Enter type of motor
2: Compact asynchronous motor 1PH7(=1PA6)/1PL6/1PH4
10: Async./Sync. IEC (international standard)
11: Async./Sync. NEMA (US standard)
12: Sync. motor, separately excited (special applications,
not v/f characteristic)
13: Sync. motor, permanently excited (special applications,
not v/f characteristic)
Enter the code number for the connected motor of the
Range 1PH7(=1PA6)/1PL6/1PH4
(see "Motor list" section)
(Automatic parameter assignment is implemented as soon as
the settings P095 = 2 and P097 > 0 have been made)
Enter the type of open/closed-loop control
0: v/f control + n control
1: v/f control
2: v/f control, textile
3: Speed control without tachometer (f control)
4: Speed control with tachometer (n control)
5: Torque control (T control)
Note:
For motor ratings over approx. 200 kW one of the
vector control types should be used (P100 > 2).
Enter the rated motor voltage in V
as per rating plate
Enter the rated motor current in A
as per rating plate
(Group drives: total of all motor currents)
Enter the motor magnetizing current as a % of the rated
motor current
If value is not known, set P103 = 0, the value is then
automatically calculated when you exit Drive setting (see r119).
Operating Instructions
Parameterizing Steps
9-53