Parameterizing Steps
P101 = ?
P102 = ?
P104=?
P105=?
P106=?
P107 = ?
P108 = ?
P109 = ?
SIEMENS
4
5
cos 0.82
3
220-240 / 380-420 V /
26.5-27.0 / 15.3-15.6 A
P114 = ?
P100=1,2
9-12
Enter the rated motor voltage in V
as per rating plate
Enter the rated motor current in A
as per rating plate
(group drives: total of all motor currents)
IEC motor: Cos (phi) as per rating plate
NEMA motor: nominal rating [Hp]
(group drives: total of all ratings)
NEMA motor: Enter the motor efficiency in %
as per rating plate
Enter the rated motor frequency in Hz
as per rating plate
Enter the rated motor speed in rpm
as per rating plate
Enter the motor pole pair number
(is automatically calculated)
3 ~Mot.
IP 55
132 M/IM B3
50 Hz
230 / 400V
7.5 kW
26.5 / 15.3 A
1455 / min
WARNING!
INCORRECT SETTINGS CAN BE DANGEROUS!
For vector control only:
Process-related boundary conditions for control
0: Standard drives
1: Torsion, gear play
2: Acceleration drives
3: Load surge
4: Smooth running characteristics
5: Efficiency optimization
6: Heavy-duty starting
7: Dynamic torque response in field-weakening range
See "Drive setting" section for description
1
1LA7133-4AA10
Nr.E H984 6148 01 002
EN 60034 Th.Cl. F
/D
60 Hz
460 V
8.6 kW
14.7 A
cos 0.83
1755 / min
440/480 V
15.0-15.2 A
SF 1.1
2
(default)
Operating Instructions
05.2006
1
2
3
4
5
C E
6SE7087-2JD60
Siemens AG
SIMOVERT MASTERDRIVES