Installation in Conformance with EMC Regulations
6-6
♦ Every SIMOVERT
MASTERDRIVES has shield
clamps to connect the signal
cable shields.
Serrated bar
Connect serrated bars
at both ends to the
cabinet housing
through the largest
possible surface area!
Fig. 6-5
Connecting signal cable shields in the cabinet
Wherever possible, intermediate terminals should not be used as they
reduce the shielding effect!
♦ For chassis units (sizes ≥ E),
the shields can be additionally
connected using cable
connectors at the shield
connecting locations.
6SE7087-2JD60
Operating Instructions
SIMOVERT MASTERDRIVES
05.2006
Cable connector
Intermediate terminals