Technical Data
Designation
Order No.
6SE70...
Rated voltage
• Input
• Output
Rated frequency
• Input
• Output:
V/f = constant
V = constant
Rated current
• Input
• Output
DC link voltage
Rated output
[kVA]
Auxiliary current supply
• Max. aux. curr. requirement[A]
Standard version at 20 V
• Max. aux. curr. requirement[A]
Maximum version at 20 V
Pulse frequency
[kHz]
Load class II to EN 60 146-1-1
Base load current
Base load duration
Overload current
Overload duration
Load class II to EN 60 146-1-1 (additional)
Base load current
Base load duration
Overload current
Overload duration
Losses, cooling, power factor
Power factor
• Line cosϕ1L
• Converter cosϕC
Efficiency
η (rated operation)
Power loss
[kW]
(at 2.5 kHz)
Cooling-air requirement [m³/s]
∆
Pressure drop
p
Sound pressure levels, types of construction, dimensions, weights
Sound pressure level [dB(A)]
Type of construction
Dimensions
[mm]
• Width
• Height
• Depth
Weight approx.
13-8
23-4EC61
23-8ED61
[V]
[Hz]
[A]
37.4
41.3
34.0
37.5
[V]
22.4 to
24.7 to
28.2
31.1
[V]
[A]
[s]
[A]
[s]
[A]
[s]
[A]
[s]
≥ 0.98
≥ 0.97
0.49
0.58
0.028
0.054
[Pa]
30
230
60
65
C
D
180
270
600
600
350
350
[kg]
21
32
Table 13-6
Air-cooled converter (part 4)
Value
24-7ED61
26-0ED61
3 AC 380 (- 15 %) to 480 (+ 10 %)
3 AC 0 up to rated input voltage
50 / 60 ± 6 %
0 to 600
8 to 300
51.7
64.9
47.0
59.0
510 (- 15 %) to 650 (+ 10 %)
31.0 to
38.9 to
39.0
49.0
DC 24 (20 - 30)
1.5
2.5
1.5 to 16 (see Fig. „Derating curves")
0.91 x rated output current
240
1.36 x rated output current
60
0.91 x rated output current
270
1.6 x rated output current
30
≥ 0.98
< 0.92 ind.
≥ 0.98
0.73
0.86
0.054
0.054
230
230
65
65
D
D
270
270
600
600
350
350
32
32
Operating Instructions
05.2006
27-2ED61
79.2
72.0
47.4 to
59.8
1.05
0.054
230
65
D
270
600
350
32
6SE7087-2JD60
Siemens AG
SIMOVERT MASTERDRIVES
Need help?