External Dynamic Brake - Mitsubishi Electric MR-J4-TM Instruction Manual

Servo amplifier melservo-j4
Hide thumbs Also See for MR-J4-TM:
Table of Contents

Advertisement

11. OPTIONS AND PERIPHERAL EQUIPMENT

11.17 External dynamic brake

CAUTION
(1) Selection of external dynamic brake
The dynamic brake is designed to bring the servo motor to a sudden stop when a power failure occurs
or the protective circuit is activated, and is built in the 7 kW or less servo amplifier. Since it is not built in
the 11 kW or more servo amplifier, purchase it separately. Assign DB (Dynamic brake interlock) to any
of CN3-9, CN3-13, and CN3-15 pins in [Pr. PD07] to [Pr. PD09].
Use an external dynamic brake for a servo amplifier of MR-J4-11KTM to MR-J4-
22KTM and MR-J4-11KTM4 to MR-J4-22KTM4. Failure to do so will cause an
accident because the servo motor does not stop immediately but coasts at an
alarm occurrence for which the servo motor does not decelerate to stop. Ensure
the safety in the entire equipment. For alarms for which the servo motor does not
decelerate to stop, refer to chapter 8.
The external dynamic brake cannot be used for compliance with SEMI-F47
standard. Do not assign DB (Dynamic brake interlock) in [Pr. PD07] to [Pr. PD09].
Failure to do so will cause the servo amplifier to become servo-off when an
instantaneous power failure occurs.
POINT
EM2 has the same function as EM1 in the torque mode.
Configure up a sequence which switches off the magnetic contactor of the
external dynamic brake after (or as soon as) the servo-on command has been
turned off at a power failure or a malfunction.
For the braking time taken when the external dynamic brake is operated, refer to
section 10.3.
The external dynamic brake is rated for a short duration. Do not use it very
frequently.
When using the 400 V class external dynamic brake, the power supply voltage is
restricted to 1-phase 380 V AC to 463 V AC (50 Hz/60 Hz).
Dynamic brake operates at occurrence of alarm, [AL. E6 Servo forced stop
warning] or when power is turned off. Do not use external dynamic brake to stop
in a normal operation as it is the function to stop in emergency.
For a machine operating at the recommended load to motor inertia ratio or less,
the estimated number of usage times of the external dynamic brake is 1000
times while the machine decelerates from the rated speed to a stop once in 10
minutes.
Be sure to enable EM1 (Forced stop 1) after servo motor stops when using EM1
(Forced stop 1) frequently in other than emergency.
Servo amplifier
MR-J4-11KTM
MR-J4-15KTM
MR-J4-22KTM
MR-J4-11KTM4
MR-J4-15KTM4
MR-J4-22KTM4
External dynamic brake
DBU-11K
DBU-15K
DBU-22K-R1
DBU-11K-4
DBU-22K-4
11 - 96

Advertisement

Table of Contents
loading

Table of Contents