8 How to program the adjustable frequency
drive
The best way to set parameters using the [Quick Menu] is by following the steps below:
1.
Press [Quick Set-up] for selecting basic motor settings, ramp times, etc.
2.
Press [Function Set-ups] for setting up the required functionality of the adjustable frequency drive - if not already covered by the settings in
[Quick Set-up].
3.
Choose between
It is recommended to do the set-up in the order listed.
Figure 8.1: Quick menu view.
8
No Operation
If
is selected in terminal 27, no connection to +24 V on terminal 27 is necessary to enable start.
If
Coast Inverse
(factory default value) is selected in Terminal 27, a connection to +24 V is necessary to enable start.
NOTE!
For detailed parameter descriptions, please see the following section on

8.1.3 Q1 My Personal Menu

Parameters defined by the user can be stored in Q1 My Personal Menu.
My Personal Menu
Select
to display only the parameters, which have been pre-selected and programmed as personal parameters. For example, a pump
or equipment OEM may have pre-programmed these to be in My Personal Menu during factory commissioning to make on-site commissioning / fine tuning
simpler. These parameters are selected in par. 0-25
20-21 Setpoint 1
20-93 PID Proportional Gain
20-94 PID Integral Time
8-2
General Settings, Open-loop Settings
My Personal Menu
MG.20.M5.22 - VLT
and
Closed-loop Settings
.
Par.
Designation
0-01
Language
1-20
Motor Power
1-22
Motor Voltage
1-23
Motor Frequency
1-24
Motor Current
1-25
Motor Nominal Speed
3-41
Ramp 1 Ramp-up Time
3-42
Ramp 1 Ramp-down Time
4-11
Motor Speed Low Limit
4-13
Motor Speed High Limit
1-29
Automatic Motor Adaptation (AMA)
Table 8.2: Quick Set-up parameters
Commonly Used Parameters - Explanations
. Up to 20 different parameters can be defined in this menu.
Q1 My Personal Menu
®
is a registered Danfoss trademark
®
VLT
AQUA Drive
Instruction Manual
[Units]
[kW]
[V]
[Hz]
[A]
[RPM]
[s]
[s]
[RPM]
[RPM]
.