8 How to program the adjustable frequency
drive
[16]
Select preset ref 6
[17]
Select preset ref 7
[18]
Select ramp 1
[19]
Select ramp 2
[22]
Run
[23]
Run reverse
[24]
Stop
[26]
Dcstop
[27]
Coast
[28]
Freeze output
[29]
Start timer 0
[30]
Start timer 1
[31]
Start timer 2
[32]
Set digital out A low
[33]
Set digital out B low
[34]
Set digital out C low
[35]
Set digital out D low
[36]
Set digital out E low
[37]
Set digital out F low
8
[38]
Set digital out A high
[39]
Set digital out B high
[40]
Set digital out C high
[41]
Set digital out D high
[42]
Set digital out E high
[43]
Set digital out F high
[60]
Reset Counter A
[61]
Reset Counter B
[70]
Start Timer 3
[71]
Start Timer 4
[72]
Start Timer 5
[73]
Start Timer 6
[74]
Start Timer 7
23-02 OFF Time
Array [10]
Range:
0 N/A*
[0 - 0 N/A]
8-44
Function:
Sets the OFF time for the timed action.
NOTE!
The adjustable frequency drive has no back-up of the clock function, and the set
date/time will reset to default (2000-01-01 00:00) after a power-down unless a
Real Time Clock module with back-up is installed. In par. 0-79
possible to program for a warning in case the clock has not been set properly,
e.g., after a power-down.
®
MG.20.M5.22 - VLT
is a registered Danfoss trademark
®
VLT
AQUA Drive
Instruction Manual
Clock Fault