7 How to operate the adjustable frequency
drive
7.1.10 Quick Transfer of Parameter Settings when using GLCP
Once the set-up of an adjustable frequency drive is complete, it is recommended to store (back up) the parameter settings in the GLCPkeypad or on a
PC via MCT 10 Set-up software Tool.
NOTE!
Stop the motor before performing any of these operations.
Data storage in LCP:
1.
Go to par. 0-50
LCP Copy
2.
Press the [OK] key.
3.
Select "All to LCP"
4.
Press the [OK] key.
All parameter settings are now stored in the GLCP indicated by the progress bar. When 100% is reached, press [OK].
The GLCP can now be connected to another adjustable frequency drive and the parameter settings copied to this adjustable frequency drive.
7
Data transfer from LCP to adjustable frequency drive:
LCP Copy
1.
Go to par. 0-50
2.
Press the [OK] key.
3.
Select "All from LCP"
4.
Press the [OK] key.
The parameter settings stored in the GLCP are now transferred to the adjustable frequency drive, as indicated by the progress bar. When 100% is reached,
press [OK].
7.1.11 Initialization to Default Settings
There are two ways to initialize the adjustable frequency drive to default: Recommended initialization and manual initialization.
Please be aware that they have different impacts according to the below description.
Recommended initialization (via par. 14-22
1.
Select par. 14-22
2.
Press [OK].
3.
Select "Initialization" (for NLCP select "2")
4.
Press [OK].
5.
Disconnect the power from the unit and wait for the display to
turn off.
6.
Reconnecting the power resets the adjustable frequency drive.
Please note that the first start-up takes a few more seconds.
7.
Press [Reset]
NOTE!
Parameters selected in par. 0-25
7-10
Operation Mode
Operation Mode
My Personal Menu
MG.20.M5.22 - VLT
)
Operation Mode
par. 14-22
par. 14-50
RFI 1
Protocol
par. 8-30
par. 8-31
Address
Baud Rate
par. 8-32
Minimum Response Delay
par. 8-35
par. 8-36
Max Response Delay
Max Inter-Char Delay
par. 8-37
par. 15-00
Operating Hours
Historic Log: Event
par. 15-20
Alarm Log: Error Code
par. 15-30
will stay present, with default factory setting.
®
is a registered Danfoss trademark
®
VLT
Instruction Manual
initializes all except:
to par. 15-05
Over Volts
Historic Log: Time
to par. 15-22
Alarm Log: Time
to par. 15-32
AQUA Drive