H3: Multi-Function Analog Inputs - YASKAWA P1000 Quick Start Manual

Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.6 H Parameters: Multi-Function Terminals
H2-oo
Function
Setting
1E
Restart enabled
1F
Motor overload alarm (oL1)
20
Drive overheat pre-alarm (oH) Closed: Heatsink temperature exceeds the parameter L8-02 value.
Mechanical weakening
22
detection
2F
Maintenance period
37
During frequency output
38
Drive enabled
39
Watt hour pulse output
3C
LOCAL/REMOTE status
3D
During speed search
3E
PID feedback low
3F
PID feedback high
4A
During KEB Ride-Thru
4C
During fast stop
4D
oH Pre-alarm time limit
4E
Braking transistor fault (rr)
4F
Braking resistor overheat (oH) Closed: The dynamic braking resistor has overheated.
50
Waiting to Run
51
Sequence timer 1
52
Sequence timer 2
53
Sequence timer 3
54
Sequence timer 4
58
Underload detection
60
Internal cooling fan alarm
71
Secondary PI Feedback Low
72
Secondary PI Feedback High Closed: The PI2 feedback level is too high.
Function 0 to 92 with inverse
100 to 192
output

H3: Multi-Function Analog Inputs

u
No.
(Addr.
Name
Hex)
H3-01
Terminal A1 Signal Level
(410)
Selection
H3-02
Terminal A1 Function
(434)
Selection
H3-03
(411)
Terminal A1 Gain Setting
H3-04
(412)
Terminal A1 Bias Setting
206
H2 Multi-Function Digital Output Settings
Closed: An automatic restart is performed
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
Closed: Mechanical weakening detected.
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require
maintenance.
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being
performed).
Closed: Multi-function input set for "Drive enable" is closed (H1-oo = 6A)
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
Open: REMOTE
Closed: LOCAL
Closed: Speed Search is being executed.
Closed: PID feedback level is too low.
Closed: The PID feedback level is too high.
Closed: KEB Ride-Thru is being performed.
Closed: A Fast Stop command has been entered from the operator or input terminals.
Closed: oH pre-alarm time limit has passed.
Closed: The built-in dynamic braking transistor failed.
Closed: b1-11 Timer is active.
Closed: Sequence timer 1 is active.
Closed: Sequence timer 2 is active.
Closed: Sequence timer 3 is active.
Closed: Sequence timer 4 is active.
Closed: Underload is detected.
Closed: Internal cooling fan alarm
Closed: PI2 feedback level is too low.
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use Jumper S1 to set input terminal A1 for a current or voltage
input signal.
Sets the function of terminal A1.
Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.
Sets the level of the input value selected in H3-02 when 0 V is input at terminal
A1.
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Description
Description
Page
Values
Page
Default: 0
110
Range: 0 to 3
Default: 0
110
Range: 0 to 26
Default: 100.0%
Min.: -999.9
110
Max.: 999.9
Default: 0.0%
Min.: -999.9
110
Max.: 999.9