No.
(Addr.
Name
Hex)
F6-30
PROFIBUS-DP Node
(3CB)
Address
F6-31
PROFIBUS-DP Clear Mode
(3CC)
Selection
F6-32
PROFIBUS-DP Data
(3CD)
Format Selection
F6-35
CANopen Node ID
(3D0)
Selection
F6-36
CANopen Communication
(3D1)
Speed
F6-50
DeviceNet MAC Address
(3C1)
F6-51
DeviceNet Communication
(3C2)
Speed
F6-52
DeviceNet PCA Setting
(3C3)
F6-53
DeviceNet PPA Setting
(3C4)
F6-54
DeviceNet Idle Mode Fault
(3C5)
Detection
F6-55
DeviceNet Baud Rate
(3C6)
Monitor
F6-56
DeviceNet Speed Scaling
(3D7)
F6-57
DeviceNet Current Scaling
(3D8)
F6-58
DeviceNet Torque Scaling
(3D9)
F6-59
DeviceNet Power Scaling
(3DA)
F6-60
DeviceNet Voltage Scaling
(3DB)
F6-61
DeviceNet Time Scaling
(3DC)
F6-62
DeviceNet Heartbeat
(3DD)
Interval
F6-63
DeviceNet Network MAC
(3DE)
ID
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Sets the node address.
0: Resets drive operation with a Clear mode command.
1: Maintains the previous operation state when Clear mode command is given.
0: PPO Type
1: Conventional
Sets the node address.
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
Selects the drive MAC address.
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from network
4: Detect automatically
Sets the format of the data set from the DeviceNet master to the drive.
Sets the format of the data set from the drive to the DeviceNet master.
0: Enabled
1: Disabled, no fault detection
Verifies the baud rate running on the network.
0: 125 kbps
1: 250 kbps
2: 500 kbps
Sets the scaling factor for the speed monitor in DeviceNet.
Sets the scaling factor for the output current monitor in DeviceNet.
Sets the scaling factor for the torque monitor in DeviceNet.
Sets the scaling factor for the power monitor in DeviceNet.
Sets the scaling factor for the voltage monitor in DeviceNet.
Sets the scaling factor for the time monitor in DeviceNet.
Sets the heartbeat interval for DeviceNet communications.
Saves and monitors settings 0 to 63 of F6-50 (DeviceNet MAC Address).
Description
B.5 E: Motor Parameters
Values
Page
Default: 0
Min.: 0
Max.: 125
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Min.: 0
Max.: 126
Default: 6
Range: 0 to 8
Default: 64
Min.: 0
Max.: 64
Default: 4
Range: 0 to 4
Default: 21
Min.: 0
Max.: 255
Default: 71
Min.: 0
Max.: 255
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 2
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: 0
Max.: 10
Default: 63
Min.: 0
Max.: 63
199