YASKAWA P1000 Quick Start Manual page 228

Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.12 U: Monitors
No.
(Addr.
Name
Hex)
U1-12
Drive Status
(4B)
U1-13
Terminal A1 Input Level
(4E)
U1-14
Terminal A2 Input Level
(4F)
U1-15
Terminal A3 Input Level
(50)
U1-16
Output Frequency after
(53)
Soft Starter
U1-18
oPE Fault Parameter
(61)
U1-19
MEMOBUS/Modbus
(66)
Error Code
U1-24
Input Pulse Monitor
(7D)
U1-25
Software Number (Flash)
(4D)
U1-26
Software No. (ROM)
(5B)
U1-29
Software No. (PWM)
(7AA)
U1-75
Time-Hour/Minute
(851)
U1-76
Date – Year
(852)
U1-77
Date – Month/Day
(853)
U1-78
Date – Week Day
(854)
<1> The number of decimal places in the parameter value depends on the drive model and the ND selection. This value has two decimal places (0.01
A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
228
Description
Verifies the drive operation status.
U1 - 12=
00000000
Displays the signal level to analog input terminal A1.
Displays the signal level to analog input terminal A2.
Displays the signal level to analog input terminal A3.
Displays output frequency with ramp time and S-curves. Units determined
by o1-03.
Displays the parameter number that caused the oPE02 operation error.
Displays the contents of a MEMOBUS/Modbus error.
U1 - 19=
00000000
Displays the frequency to pulse train input terminal RP.
FLASH ID
ROM ID
PWM ID
Displays the current time (Hours and Minutes).
Displays the current year.
Displays the current date (Month and Date).
Displays the current date of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
1
During run
1
During zero-speed
1
During REV
1
During fault reset
signal input
1
During speed agree
1
Drive ready
1
During alarm
detection
1
During fault detection
1
CRC Error
1
Data Length Error
0
Not Used
1
Parity Error
1
Overrun Error
1
Framing Error
1
Timed Out
0
Not Used
Analog Output Level
Unit
No signal output
available
10 V: 100%
0.1%
10 V: 100%
0.1%
10 V: 100%
0.1%
10 V: Max frequency
0.01 Hz
No signal output
available
No signal output
available
Determined by H6-02
1 Hz
No signal output
available
No signal output
available
No signal output
available
No signal output
available
No signal output
available
No signal output
available
No signal output
available

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents