4.6 Basic Drive Setup Adjustments
10 V
Output Voltage
3 V
0 V
0%
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
n
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
No.
H4-07
H4-08
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
L3-01: Stall Prevention Selection during Acceleration
n
Stall Prevention during acceleration prevents tripping with overcurrent (oC), motor overload (oL1), or drive overload (oL2)
faults common when accelerating with heavy loads.
L3-01 determines the type of Stall prevention the drive should use during acceleration.
No.
L3-01
Setting 0: Disabled
No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to speed
fast enough, causing an overload fault.
Setting 1: Enabled
Enables Stall Prevention during acceleration.
Acceleration is reduced when the output current value exceeds 85% of the level set to parameter L3-02 for a longer than the
time set to L3-27. The acceleration stops when the current exceeds L3-02. Acceleration continues when the current falls below
L3-02 for longer than the time set to L3-27.
The Stall Prevention level is automatically reduced in the constant power range.
Acceleration on page
115.
114
H4-07, 08 = 0
100%
Monitor Value
Figure 4.26 Analog Output Gain and Bias Setting Example 3
Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection
Name
Stall Prevention Selection during Acceleration
Output Voltage
Bias 30%
Gain 100%
-100%
Bias 0%
Gain 100%
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Gain = 100%
H4-07, 08 = 1
Bias = 30%
10V
Gain = 100%
Bias = 0%
3 V
100%
Monitor Value
-4 V
-10 V
Setting Range
0 to 2
0 to 2
Setting Range
0 to 2
Refer to L3-03: Stall Prevention Limit during
Default
0
0
Default
1