4.6 Basic Drive Setup Adjustments
b2-01: DC Injection Braking Start Frequency
n
Active when "Ramp to Stop" is selected as the stopping method (b1-03 = 0).
No.
b2-01
V/f Control
Sets the starting frequency for DC Injection Braking at Stop. When the output frequency falls below the setting of b2-01, DC
Injection Braking is enabled for the time set in parameter b2-04.
Note:
If b2-01 is set to a smaller value than E1-09 (Minimum Frequency), then DC Injection Braking will begin when the frequency falls to the
E1-09 value.
b3-01: Speed Search Selection at Start
n
Determines if Speed Search is automatically performed when a Run command is issued.
No.
b3-01
Setting 0: Disabled
This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed
Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Setting 1: Enabled
This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search
is complete.

EZ Sleep/Wake-up Function

u
To enable EZ Sleep/Wake-up functionality on the drive, first set parameter b5-89 to 1. The default setting for b5-89 is 0, which
disables the EZ Sleep functionality and related parameters, except for parameter b5-91, EZ Sleep Minimum Speed.
Setting b5-89 to 1 disables the existing PID Sleep function (b5-15) and enables the EZ Sleep/Wake-up functionality.
EZ Sleep and Minimum Speed Units
Parameter b5-90, EZ Sleep Unit, determines the unit, range, and resolution of parameters b5-92 and b5-93. When set to Hz,
the range is 0.1 to 400.0 Hz. When set to RPM, the range is 0 to 24000 RPM. Changing b5-90 will NOT automatically re-
scale the values of b5-92 and b5-93.
Minimum Speed
96
Run wait time t
Active deceleration time
Min Baseblock Time (L2-03)
Min output
frequency
Figure 4.12 Run Wait Time Depending on Output Frequency
Name
DC Injection Braking Start Frequency
Output
Frequency
Figure 4.13 DC Injection Braking at Stop for V/f
Parameter Name
Speed Search Selection at Start
Output frequency
when Stop command
was entered
DC Injection
Braking
E1-09 Min. Frequency
b2-01 Zero Speed Level
b2-04
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
100%
(Max output
frequency)
Setting Range
0.0 to 10.0 Hz
Time
Setting Range
0, 1
Default
0.5 Hz
Default
0