Table of Contents

Advertisement

3.6 Main Circuit Wiring
Drive Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1
5A0242
⊕3
When connecting peripheral devices or options to terminals ⊖, ⊕1, ⊕3, B1, and B2 , refer to the instruction manual for each device. For
Note:
more information, contact Yaskawa or your nearest sales representative.

Main Circuit Terminal and Motor Wiring

u
This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
Electrical Shock Hazard. Do not connect the AC power line to the output terminals of the drive. Failure to comply could result
WARNING!
in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.
When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should
NOTICE:
match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE:
Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to
comply may result in abnormal operation of drive and nearby equipment.
NOTICE:
Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage
to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.
Cable Length Between Drive and Motor
n
Voltage drop along the motor cable may cause reduced motor torque when the wiring between the drive and the motor is too
long, especially at low frequency output. This can also be a problem when motors are connected in parallel with a fairly long
motor cable. Drive output current will increase as the leakage current from the cable increases. An increase in leakage current
may trigger an overcurrent situation and weaken the accuracy of the current detection.
Adjust the drive carrier frequency according to
configuration, reduce the ground currents.
Cable Length
Carrier Frequency
Note:
When setting carrier frequency for drives running multiple motors, calculate cable length as the total wiring distance to all connected motors.
Ground Wiring
n
Follow the precautions below when wiring the ground for one drive or a series of drives.
Electrical Shock Hazard. Make sure the protective earthing conductor complies with technical standards and local safety
WARNING!
regulations. Because the leakage current exceeds 3.5 mA in models 4A0414 and larger, IEC/EN 61800-5-1 states that either the power
supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor
with a cross-section of at least 10 mm
Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize
WARNING!
the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could
result in death or serious injury.
Electrical Shock Hazard. Be sure to ground the drive ground terminal (200 V class: ground to 100 Ω or less; 400 V class: ground
WARNING!
to 10 Ω or less; 600 V class: ground to 10 Ω or less). Improper equipment grounding could result in death or serious injury by contacting
ungrounded electrical equipment.
Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper
NOTICE:
equipment grounding could result in drive or equipment malfunction due to electrical interference.
When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in
NOTICE:
abnormal operation of drive or equipment.
Refer to
Figure 3.24
when using multiple drives. Do not loop the ground wire.
64
Recomm. Gauge
Terminal
AWG, kcmil
Table
Refer to C6-02: Carrier Frequency Selection on page
Table 3.6 Cable Length Between Drive and Motor
50 m or less
15 kHz or less
2
(Cu) or 16 mm
2
(Al) must be used. Failure to comply may result in death or serious injury.
Wire Range
AWG, kcmil
400
2/0 to 600
350
2/0 to 600
2/0 to 500
250 to 300
1
1 to 350
3.6. If the motor wiring distance exceeds 100 m because of the system
100 m or less
5 kHz or less
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Screw
Tightening Torque
Size
N·m (lb.in.)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
100.
Greater than 100 m
2 kHz or less