V/f Pattern Settings (E1-03)
n
The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference. There are 15 different predefined
V/f patterns (setting 0 to E) from which to select, each with varying voltage profiles, saturation levels (frequency at which
maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern is available (setting F) that
requires the user to create the pattern using parameters E1-04 through E1-10.
E1-03: V/f Pattern Selection
n
Selects the V/f pattern for the drive and motor from 15 predefined patterns or creates a custom V/f pattern.
No.
E1-03
<1> Parameter is not reset to the default value when the drive is initialized using A1-03.
Setting a Predefined V/f Pattern (Setting 0 to E)
Choose the V/f pattern that best meets the application demands from
V/f Control modes. Set the correct value to E1-03. Parameters E1-04 to E1-13 can only be monitored, not changed.
Note:
1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.
Setting
Specification
0
50 Hz
1
60 Hz
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Variable torque 1
5
50 Hz, Variable torque 2
6
60 Hz, Variable torque 1
7
60 Hz, Variable torque 2
8
50 Hz, mid starting torque
9
50 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
F
60 Hz
<1>
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are the same as those of setting 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 2A0004 to 2A0021, 4A0002 to 4A0011, and 5A0003 to 5A0009
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V drives.
Setting = 0
50 Hz
200
15
9
0
1.3 2.5
50
Frequency (Hz)
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Parameter Name
V/f Pattern Selection
Table 4.14 Predefined V/f Patterns
Characteristic
Constant torque
Variable torque
High starting torque
Constant output
Constant torque
Table 4.15 Constant Torque Characteristics, Settings 0 to 3
Setting = 1
60 Hz
200
15
9
0
1.5 3
60
Frequency (Hz)
4.6 Basic Drive Setup Adjustments
Setting Range
0 to F
Table
4.14. These settings are available only in
For general purpose applications. Torque remains constant
regardless of changes to speed.
For fans, pumps, and other applications where the required
torque changes as a function of the speed.
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
Output voltage is constant when operating at greater than
60 Hz.
For general purpose applications. Torque remains constant
regardless of changes to speed.
Setting = 2
60 Hz
200
15
9
0
1.5 3
50
60
Frequency (Hz)
Default
<1>
F
Application
Setting = 3
72 Hz
200
15
9
0
1.5 3
60
72
Frequency (Hz)
103