YASKAWA P1000 Quick Start Manual page 140

Hide thumbs Also See for P1000:
Table of Contents

Advertisement

5.2 Fault Detection
Load is too heavy
Internal cooling fan is stopped
Digital Operator Display
Cause
Surrounding temperature is too high
Load is too heavy
Digital Operator Display
<1>
Cause
Motor has overheated
<1> Detected in models 4A0930 and 4A1200.
Digital Operator Display
Cause
Load is too heavy
Cycle times are too short during acceleration
and deceleration
A general-purpose motor is driven below the
rated speed with a high load
The output voltage is too high
The wrong motor rated current is set to E2-01
The base frequency is set incorrectly
The electrical thermal protection
characteristics and motor overload
characteristics do not match
The electrical thermal relay is operating at the
wrong level
Motor overheated by overexcitation operation
140
• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-02).
• Replace the cooling fan.
• After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.
Overheat 1 (Heatsink Overheat)
oH1
The heatsink temperature exceeded the drive overheat level. Overheat level is determined by drive
capacity (o2-04).
• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.
• Measure the output current.
• Lower the carrier frequency (C6-02).
• Reduce the load.
Motor Overheat (NTC Input)
oH5
The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2)
• Reduce the load.
• Check the ambient temperature.
Motor Overload
oL1
The electronic motor overload protection tripped
Reduce the load.
Increase the acceleration and deceleration times (C1-01 through C1-04).
• Reduce the load.
• Increase the speed.
• If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
• Adjust the user-set V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
• Check the motor-rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
• Check the rated frequency indicated on the motor nameplate.
• Enter the rated frequency to E1-06 (Base Frequency).
• Check the motor characteristics.
• Correct the type of motor protection that has been selected (L1-01).
• Install an external thermal relay.
• Check the current rating listed on the motor nameplate.
• Check the value set for the motor rated current (E2-01).
• Overexcitation increases the motor loss and the motor temperature. Excessive duration of
overexcitation may cause motor damage. Prevent excessive overexcitation operation or apply proper
cooling to the motor.
• Reduce the excitation deceleration gain (n3-13).
• Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents