YASKAWA P1000 Quick Start Manual page 132

Hide thumbs Also See for P1000:
Table of Contents

Advertisement

4.12 Fan and Pump Application Preset Details
No.
L5-04
o1-06: User Monitor Selection Mode
n
Select between standard sequential monitors or selectable monitors to be displayed on the 2nd and 3rd lines of the digital
operator display.
Use parameters o1-07 and o1-08 to select and fix the second and third monitors shown in the Home (Frequency Reference)
and Monitor screen to ensure that those monitors are always visible when scrolling through the monitor list.
No.
o1-06
Setting 0: 3 Mon Sequential (displays the next 2 sequential monitors)
Setting 1: 3 Mon Selectable (set by o1-07 and o1-08)
o1-07: Second Line User Monitor Selection
n
Selects the monitor that is shown in the second line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set "403" to display
monitor parameter U4-03.
No.
o1-07
o1-08: Third Line User Monitor Selection
n
Selects the monitor that is shown in the third line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set "403" to display
monitor parameter U4-03.
No.
o1-08
132
Name
Fault Reset Interval Time
Name
User Monitor Selection Mode
Name
Second Line User Monitor Selection
Name
Second Line User Monitor Selection
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Setting Range
0.5 to 600.0 s
Setting Range
0, 1
Setting Range
101 to 799
Setting Range
101 to 799
Default
10.0 s
Default
0
Default
102
Default
103

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents