B3: Speed Search - YASKAWA P1000 Quick Start Manual

Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.2 b: Application
No.
(Addr.
Name
Hex)
b2-04
DC Injection Braking Time
(18C)
at Stop
u

b3: Speed Search

No.
(Addr
Name
Hex.)
b3-01
Speed Search Selection at
(191)
Start
b3-02
Speed Search Deactivation
(192)
Current
b3-03
Speed Search Deceleration
(193)
Time
b3-04
V/f Gain during Speed
(194)
Search
b3-05
Speed Search Delay Time
(195)
b3-06
Output Current 1 during
(196)
Speed Search
Output Current 2 during
b3-07
Speed Search (Speed
(197)
Estimation Type)
Current Control Gain during
b3-08
Speed Search (Speed
(198)
Estimation Type)
b3-10
Speed Search Detection
(19A)
Compensation Gain
b3-12
Minimum Current Detection
(19C)
Level during Speed Search
b3-14
Bi-Directional Speed Search
(19E)
Selection
b3-17
Speed Search Restart
(1F0)
Current Level
b3-18
Speed Search Restart
(1F1)
Detection Time
b3-19
Number of Speed Search
(1F2)
Restarts
b3-24
Speed Search Method
(1C0)
Selection
b3-25
Speed Search Wait Time
(1C8)
b3-26
Direction Determining
(1C7)
Level
b3-27
Start Speed Search Select
(1C9)
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
186
Sets DC Injection Braking time at stop.
0: Disabled
1: Enabled
Sets the current level at which the speed is assumed to be detected and Speed
Search is ended. Set as a percentage of the drive rated current.
Sets output frequency reduction time during Speed Search.
Determines how much to lower the V/f ratio during Speed Search.
Output voltage during Speed Search equals the V/f setting multiplied by b3-04.
When using an external contactor on the output side, b3-05 delays executing
Speed Search after a momentary power loss to allow time for the contactor to
close.
Sets the current injected to the motor at the beginning of Speed Estimation
Speed Search. Set as a coefficient for the motor rated current.
Sets the amount of output current during Speed Estimation Speed Search as a
coefficient for the no-load current.
Sets the proportional gain for the current controller during Speed Search.
Sets the gain which is applied to the speed detected by Speed Estimation Speed
Search before the motor is reaccelerated. Increase this setting if ov occurs
when performing Speed Search after a relatively long period of baseblock.
Sets the minimum current detection level during Speed Search.
0: Disabled (uses the direction of the frequency reference)
1: Enabled (drive detects which way the motor is rotating)
Sets the Speed Search restart current level as a percentage of the drive rated
current.
Sets the time to detect Speed Search restart.
Sets the number of times the drive can attempt to restart when performing
Speed Search.
0: Current Detection
1: Speed Estimation
Sets the time the drive must wait between each Speed Search restart attempt. Default: 0.5 s
Sets the level that determines the direction of motor rotation.
Selects a condition to activate Speed Search Selection at Start (b3-01) or
External Speed Search Command 1 or 2 from the multi-function input.
0: Triggered when a Run command is issued (normal).
1: Triggered when an external baseblock is released.
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Description
Description
Values
Page
Default: 0.50 s
Min.: 0.00
Max.: 10.00
Values
Page
Default: 0
96
Range: 0, 1
Default: 120%
Min.: 0
Max.: 200
Default: 2.0 s
Min.: 0.1
Max.: 10.0
<1>
Default:
Min.: 10%
Max.: 100%
Default: 0.2 s
Min.: 0.0
Max.: 100.0
<1>
Default:
Min.: 0.0
Max.: 2.0
<1>
Default:
Min.: 0.0
Max.: 5.0
Default: 0.8
Min.: 0.00
Max.: 6.00
Default: 1.05
Min.: 1.00
Max.: 1.20
Default: 6.0
Min.: 2.0
Max.: 10.0
Default: 1
Range: 0, 1
Default: 150%
Min.: 0
Max.: 200
Default: 0.10 s
Min.: 0.00
Max.: 1.00
Default: 3
Min.: 0
Max.: 10
Default: 0
Range: 0, 1
Min.: 0.0
Max.: 30.0
<1>
Default:
Min.: 40
Max.: 60000
Default: 0
Range: 0, 1