4.6 Basic Drive Setup Adjustments
b1-01: Frequency Reference Selection 1
n
Selects the frequency reference source 1 for the REMOTE mode.
Note:
1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
LED on the digital operator will light and the STOP indicator will flash.
2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
No.
b1-01
Setting 0: Operator keypad
Using this setting, the frequency reference can be input by:
• switching between the multi-speed references in the d1-oo parameters.
• entering the frequency reference on the operator keypad.
Setting 1: Terminals (analog input terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in
used.
Terminal
Signal Level
0 to 10 Vdc
A1
-10 to +10 Vdc
0 to 10 Vdc
A2
-10 to +10 Vdc
0 to 10 Vdc
A3
-10 to +10 Vdc
0 to 10 V
2 k
Current Input
Input terminals, A1, A2, and A3 can accept a current input signal. Refer to
current input.
Signal
Terminal
Level
Signal Level Selection Function Selection
4 to 20 mA
A2
0 to 20 mA
92
Parameter Name
Frequency Reference Selection 1
Table 4.8 Analog Input Settings for Frequency Reference Using Voltage Signals
Signal Level
Function Selection
Selection
H3-01 = 0
(Frequency Reference Bias)
H3-01 = 1
H3-09 = 0
(Frequency Reference Bias)
H3-09 = 1
H3-05 = 0
(Frequency Reference Bias)
H3-05 = 1
Drive
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
Figure 4.6 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Table 4.9 Analog Input Settings for Frequency Reference Using a Current Signal
Parameter Settings
H3-09 = 2
H3-10 = 0
(Frequency Bias)
H3-09 = 3
Parameter Settings
Gain
H3-02 = 0
H3-03
H3-10 = 0
H3-11
H3-06 = 0
H3-07
+10 V
4 k
Customer
+/- 10 V
Supply
OR
-10 V
Common
Table 4.9
Gain
H3-11
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Setting Range
0 to 4
Table 4.8
Bias
H3-04
Set jumper S1 on the terminal
H3-12
board to "V" for voltage input.
Set DIP switch S4 on the
H3-08
terminal board to "AI".
Drive
+V 10.5 V, 20 mA power supply
-10 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
for an example to set terminal A2 for
Bias
Make sure to set jumper S1 on the
H3-12
terminal board to "I" for current
input.
Default
1
for the input
Notes
Notes