YASKAWA P1000 Quick Start Manual page 111

Hide thumbs Also See for P1000:
Table of Contents

Advertisement

A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since
the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04
above 5 Vdc.
• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.
H3-05: Terminal A3 Signal Level Selection
n
Determines the function assigned to analog input terminal A3.
No.
H3-05
Terminal A3 Signal Level Selection
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. See the explanation provided for H3-01.
Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc. See the explanation provided for H3-01.
110.
Setting 2: 4 to 20 mA
Setting 3: 0 to 20 mA
H3-06: Terminal A3 Function Selection
n
Determines the function assigned to analog input terminal A3.
No.
H3-06
H3-07, H3-08: Terminal A3 Gain and Bias Setting
n
Parameter H3-07 sets the level of the selected input value that is equal to 10 Vdc input at terminal A3 (gain).
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
H3-01 = 0
Gain = 200 %
Frequency
reference
100 %
E1-04
Bias = 0 %
0 V
5 V
Figure 4.23 Frequency Reference Setting by Analog Input with Increased Gain
H3-01 = 0
100 %
Frequency
H3-01 = 0
reference
0
2.0 V
Analog Input
-25%
Voltage
H3-01 = 1
Figure 4.24 Frequency Reference Setting by Analog Input with Negative Bias
Name
Name
Terminal A3 Function Selection
H3-01 = 1
Gain = 200 %
100%
E1-04
-10 V
-5 V
10 V
H3-01 = 1
100%
-10 V
-6.0 V
10 V
E1-04
Refer to Setting 0: 0 to 10 Vdc on page
Refer to Setting 1: 0 to 10 Vdc Bipolar on page
4.6 Basic Drive Setup Adjustments
5 V
0 V
10 V
-100%
E1-04
Gain = -200 %
10 V
2.0 V
Analog Input
-25%
Voltage
-100%
-150%
Setting Range
0 to 3
Setting Range
0 to 26
Default
0
110.
4
Default
2
111

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents