B.12 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.

U1: Operation Status Monitors

u
No.
(Addr.
Name
Hex)
U1-01
Frequency Reference
(40)
U1-02
Output Frequency
(41)
U1-03
Output Current
(42)
U1-04
Control Method
(43)
U1-06
Output Voltage Reference
(45)
U1-07
DC Bus Voltage
(46)
U1-08
Output Power
(47)
U1-10
Input Terminal Status
(49)
U1-11
Output Terminal Status
(4A)
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Description
Monitors the frequency reference. Display units are determined by o1-03. 10 V: Max frequency
Displays the output frequency. Display units are determined by o1-03.
Displays the output current.
0: V/f Control
Displays the output voltage.
Displays the DC bus voltage.
Displays the output power (this value is calculated internally).
Displays the input terminal status.
U1 - 10= 00000000
Displays the output terminal status.
U1 - 11=
00000000
1
Digital input 1
(terminal S1 enabled)
1
Digital input 2
(terminal S2 enabled)
1
Digital input 3
(terminal S3 enabled)
1
Digital input 4
(terminal S4 enabled)
1
Digital input 5
(terminal S5 enabled)
1
Digital input 6
(terminal S6 enabled)
1
Digital input 7
(terminal S7 enabled)
1
Digital input 8
(terminal S8 enabled)
1
Multi-Function
Digital Output
(terminal M1-M2)
1
Multi-Function
Digital Output
(terminal M3-M4)
1
Multi-Function
Digital Output
(terminal MD-ME-MF)
0
Not Used
1
Fault Relay
(terminal MA-MC closed
MA-MC open)
B.12 U: Monitors
Analog Output Level
Unit
0.01 Hz
10 V: Max frequency
0.01 Hz
10 V: Drive rated
<1> <2>
current
No signal output
available
<3>
0.1 Vac
10 V: 200 Vrms
<3>
1 Vdc
10 V: 400 V
10 V: Drive capacity
<4>
(motor capacity) kW
No signal output
available
No signal output
available
227
B