3.1 Standard Connection Diagram

3.1

Standard Connection Diagram

Connect the drive and peripheral devices as shown in
without connecting digital I/O wiring. This section does not discuss drive operation;
Operation on page 77
for instructions on operating the drive.
Inadequate wiring could result in damage to the drive. Install adequate branch circuit short circuit protection per applicable codes.
NOTICE:
The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac maximum (200 V class),
480 Vac maximum (400 V class), 600 Vac maximum (600 V class).
NOTICE:
When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to the motor
insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.
NOTICE:
Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
Note:
The minimum load for the relay outputs M1-M2, M3-M4, MA-MB-MC, and MD-ME-MF is 10 mA.
42
Figure
3.1. It is possible to set and run the drive via the digital operator
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Refer to Start-Up Programming &