Floor Loading Requirements; Weight Of Components - GE Discovery NM/CT 670 Instructions Manual

Nuclear medicine imaging system
Table of Contents

Advertisement

Equipment Description and General Construction Requirements

2.3.1.2 Floor Loading Requirements

Table 2-2: Weight of Components
Component
NM gantry (with HEGP
collimators mounted on
system)
Patient table
Storage cabinet, including
tools (optional)
CT gantry
CT PDU
CT NIO console
AW workstation (optional)
Collimator cart (with 2 HEGPs
on cart)
NM Acquisition station, ECG
Trigger Monitor, Operator
chair, Contrast Injector
Personnel and patient
Discovery NM/CT 670 – Standard Integration Instructions
5483063-1EN, Rev.2, ©2015 GE Healthcare
Weight (kg)
Weight
(lb)
2190
4828
565
861246
< 130
< 287
1850
4078
D670/BSE 350
D670/BSE 772
D670/OPT 370
D670/OPT 815
89
196
30
66
330
728
(insignificant)
< 500
< 1102
Load Distribution
4 pads, Ø83 mm each:
+845 kg each on front pads
+250 kg each on rear pads
4 wheels + axis anchored
to floor
4 legs
4 wheels; anchored to floor
4 wheels
Placed on desk
4 wheels
Variable
2-28
2.3 Room Structural Requirements
2.3.1 Floor Requirements
Comments
Weight of table without
patient
COG point at 99 cm height;
may be more than one
collimator cart in scan room
Normally 3-4 people in room
during scan/service operations

Hide quick links:

Advertisement

Table of Contents
loading