Electrical Requirements
Table 5-3: D670 Minimum Feeder Wire Size
Feeder Length (MDA to MDP)
Feet (Meters)
50 (15)
100 (30)
150 (46)
200 (61)
250 (76)
300 (91)
350 (107)
400 (122)
Feeder Length (PIDB to
CT PDU) Feet (Meters)
32 (9.7536)
Discovery NM/CT 670 – Standard Integration Instructions
5483063-1EN, Rev.2, ©2015 GE Healthcare
Minimum feeder wire size, AWG or MCM (Sq. MM)/ VAC
380 VAC
400 VAC
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
2 (35)
1 (45)
1 (45)
1/0 (55)
1/0 (55)
2/0 (70)
1/0 (55)
2/0 (70)
2/0 (70)
Minimum sub-feeder wire size, AWG or MCM (Sq. MM)/ VAC
380 VAC
400 VAC
2 (35)
2 (35)
5-4
420 VAC
440 VAC
3 (30)
3 (30)
3 (30)
3 (30)
3 (30)
3 (30)
3 (30)
3 (30)
2 (35)
2 (35)
1 (45)
1 (45)
1/0 (55)
1 (45)
1/0 (55)
1/0 (55)
420 VAC
440 VAC
3 (30)
3 (30)
5.1 Power Feed
460 VAC
480 VAC
3 (30)
3 (30)
3 (30)
3 (30)
3 (30)
3 (30)
3 (30)
3 (30)
2 (35)
3 (30)
2 (35)
2 (35)
1 (45)
1 (45)
1/0 (55)
1 (45)
460 VAC
480 VAC
3 (30)
3 (30)