Delta VFD-B User Manual page 72

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Parameter
Explanation
08-14
Auto Restart After
Fault
08-15
Auto Energy Saving
08-16
AVR Function
Software Brake
08-17
Level
Base-block Speed
08-18
Search
Speed Search
08-19
during Start-up
Speed Search
08-20
Frequency during
Start-up
Auto Reset Time at
08-21
Restart after Fault
Compensation
08-22
Coefficient for Motor
Instability
Group 9 Communication Parameters
Parameter
Explanation
Communication
09-00
Address
09-01
Transmission Speed
Transmission Fault
09-02
Treatment
09-03
Time-out Detection
Communication
09-04
Protocol
Revision July 2008, BE16, SW V4.08 & V5.00
Settings
00 to 10 (00=disable)
00: Disable
01: Enable
00: AVR function enable
01: AVR function disable
02: AVR function disable for decel.
230V series: 370 to 430V
460V series: 740 to 860V
575V series: 925 to1075V
00: Speed search starts with last frequency
command
01: Starts with minimum output frequency
00: Speed search disable
01: Speed search enable
00: Setting frequency
01: Maximum operation frequency (01-00)
00 to 60000 sec
00~1000
Settings
01 to 254
00: Baud rate 4800bps
01: Baud rate 9600bps
02: Baud rate 19200bps
03: Baud rate 38400bps
00: Warn and keep operating
01: Warn and ramp to stop
02: Warn and coast to stop
03: No warning and keep operating
0.0 ~ 60.0 seconds
0.0: Disable
00: 7,N,2 (Modbus, ASCII)
01: 7,E,1 (Modbus, ASCII)
02: 7,O,1 (Modbus, ASCII)
03: 8,N,2 (Modbus, RTU)
04: 8,E,1 (Modbus, RTU)
05: 8,O,1 (Modbus, RTU)
Chapter 5 Parameters|VFD-B Series
Factory
Setting
00
00
00
380
760
950
00
00
00
600
00
Factory
Setting
01
01
03
0.0
00
Customer
Customer
5-15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents