Basic Parameters - Delta VFD-B User Manual

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Parameter
Explanation
00-10
Reserved
Group 1 Basic Parameters
Parameter
Explanation
Maximum Output
01-00
Frequency (Fmax)
Maximum Voltage
01-01
Frequency (Fbase)
Maximum Output
01-02
Voltage (Vmax)
Mid-Point Frequency
01-03
(Fmid)
Mid-Point Voltage
01-04
(Vmid)
Minimum Output
01-05
Frequency (Fmin)
Minimum Output
01-06
Voltage (Vmin)
Output Frequency
01-07
Upper Limit
Output Frequency
01-08
Lower Limit
01-09
Accel Time 1
01-10
Decel Time 1
01-11
Accel Time 2
01-12
Decel Time 2
01-09 ~ 01-12: Factory setting for models of 30hp (22kW) and above is 60sec.
01-13
Jog Acceleration
Time
01-14
Jog Frequency
Auto acceleration /
deceleration (refer to
01-15
Accel/Decel time
setting)
Acceleration S-
01-16
Curve
Deceleration S-
01-17
Curve
01-18
Accel Time 3
01-19
Decel Time 3
01-20
Accel Time 4
Revision July 2008, BE16, SW V4.08 & V5.00
Settings
Settings
50.00 to 400.00 Hz
0.10 to 400.00 Hz
230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
575V series: 0.1V to 637.0V
0.10 to 400.00 Hz
230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
575V series: 0.1V to 637.0V
0.10 to 400.00 Hz
230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
575V series: 0.1V to 637.0V
1 to 120%
0 to100 %
0.01 to 3600.0 sec
0.01 to 3600.0 sec
0.01 to 3600.0 sec
0.01 to 3600.0 sec
0.1 to 3600.0 sec
0.10 Hz to 400.00 Hz
00: Linear Accel/Decel
01: Auto Accel, Linear Decel
02: Linear Accel, Auto Decel
03: Auto Accel/Decel (Set by load)
04: Auto Accel/Decel (set by Accel/Decel
Time setting)
00 to 07
00 to 07
0.01 to 3600.0 sec
0.01 to 3600.0 sec
0.01 to 3600.0 sec
Chapter 5 Parameters|VFD-B Series
Factory
Setting
Factory
Setting
60.00
60.00
220.0
440.0
575.0
0.50
1.7
3.4
4.8
0.50
1.7
3.4
4.8
100
0
10.0
10.0
10.0
10.0
1.0
6.00
00
00
00
10.0
10.0
10.0
Customer
Customer
5-3