Chapter 5 Parameters|VFD-B Series
Parameter
Explanation
01-21
Decel Time 4
01-18 ~ 01-21: Factory setting for models of 30hp (22kW) and above is 60sec.
01-22
Jog Deceleration
Time
Accel/Decel Time
01-23
Unit
Group 2 Operation Method Parameters
Parameter
Explanation
Source of First
02-00
Master Frequency
Command
Source of First
02-01
Operation Command
02-02
Stop Method
PWM Carrier
02-03
Frequency
Selections
5-4
Settings
0.01 to 3600.0 sec
0.1 to 3600.0 sec
00: Unit: 1 sec
01: Unit: 0.1 sec
02: Unit: 0.01 sec
Settings
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
05: RS-485 serial communication (RJ-11).
Last used frequency not saved.
06: Combined use of master and auxiliary
frequency command
(See Pr. 02-10 to 02-12)
00: Digital keypad (PU01)
01: External terminals. Keypad STOP/RESET
enabled.
02: External terminals. Keypad STOP/RESET
disabled.
03: RS-485 serial communication (RJ-11).
Keypad STOP/RESET enabled.
04: RS-485 serial communication (RJ-11).
Keypad STOP/RESET disabled.
00: STOP: ramp to stop; E.F.: coast to stop
01: STOP: coast to stop; E.F.: coast to stop
02: STOP: ramp to stop; E.F.: ramp to stop
03: STOP: coast to stop; E.F.: ramp to stop
230V&460V:1-5hp/0.75-3.7kW: 1-15kHz
7.5-25hp/5.5-18.5kW: 01-15kHz
30-60hp/22-45kW: 01-09kHz
75-100hp/55-75kW: 01-06kHz
575V: 1-15hp/0.75-11kW: 01-10 kHz
20-60hp/15-45kW: 01-08 kHz
75-100hp/55-75kW: 01-06kHz
Factory
Revision July 2008, BE16, SW V4.08 & V5.00
Customer
Setting
10.0
1.0
01
Factory
Customer
Setting
00
00
00
15
09
06
06
06
06
06