Time Delay before Stopping the Auxiliary Motor

Settings
The number of Multi-function Output terminals set to 16, 17, 18 decides the number of auxiliary
motors. The maximum is three.
The start/stop frequency of the auxiliary motor must have a minimum of 5Hz difference.
The start/stop delay time can prevent the AC motor drive from overloaded during
starting/stopping.
These parameters determine the starting sequence of auxiliary motors.
The auxiliary motor started first will be stopped first.
Example: Start sequence: motor 1 -> motor 2 -> motor 3
Stop sequence: motor 1 -> motor 2 -> motor 3
The flowchart of auxiliary motor start/stop sequence:
Pr.11-01 Start-up frequency = 50 Hz, Pr.11-02 Stop frequency = 20 Hz
Pr.11-03 Time delay before start up = 10 sec, Pr.11-04 Time delay before stopping = 5 sec
5-102
0.0 to 3600.0 sec
Output frequency of
master motor
50
H
Output Freq.
YES
11-03
Start delay timer
of auxiliary
motor begins
NO
10 sec
Counter
YES
Start the
auxiliary motor
in order
H
20
NO
Output Freq.
YES
11-04
Stop delay timer
of auxiliary
motor begins
Counter
5 sec
YES
Stop the
auxiliary motor
in order
Revision July 2008, BE16, SW V4.08 & V5.00
Unit: 0.1
Factory Setting: 0.0