Over-Torque Detection Mode (Ol2); Over-Torque Detection Level (Ol2); Over-Torque Detection Time (Ol2) - Delta VFD-B User Manual

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

06 - 03

Over-Torque Detection Mode (OL2)

Settings
This parameter determines the operation mode of the drive after the over-torque (OL2) is
detected via the following method: if the output current exceeds the over-torque detection level
(Pr.06-04) longer than the setting of Pr.06-05 Over-Torque Detection Time, the warning
message "OL2" is displayed. If a Multi-Functional Output Terminal is set to over-torque
detection (Pr.03-00~03-03=04), the output is on. Please refer to Pr.03-00~03-03 for details.
06 - 04

Over-Torque Detection Level (OL2)

Settings
This setting is proportional to the Rated Output Current of the drive.
06 - 05

Over-Torque Detection Time (OL2)

Settings
This parameter sets the time for how long over-torque must be detected before "OL2" is
displayed.
Revision July 2008, BE16, SW V4.08 & V5.00
Over-Current
Detection
Level
06-02
over-current stall prevention during operation
00
Over-Torque detection disabled.
01
Over-Torque detection enabled during constant speed operation.
After over-torque is detected, keep running until OL1 or OL occurs.
02
Over-Torque detection enabled during constant speed operation.
After over-torque is detected, stop running.
03
Over-Torque detection enabled during acceleration. After over-
torque is detected, keep running until OL1 or OL occurs.
04
Over-Torque detection enabled during acceleration. After over-
torque is detected, stop running.
10 to 200%
0.1 to 60.0 sec
Over-Current Stall
Prevention during
Operation, output
frequency decrease
Output
Frequency
Chapter 5 Parameters|VFD-B Series
Output Current
Factory Setting: 00
Factory Setting: 150
Factory Setting: 0.1
Unit: 1
Unit: 0.1
5-67