Parameter
Explanation
Motor Direction
02-04
Control
2-wire/3-wire
02-05
Operation Control
Modes
02-06
Line Start Lockout
Loss of ACI Signal
02-07
(4-20mA)
02-08
Up/Down Mode
Accel/Decel Rate of
Change of
02-09
UP/DOWN
Operation with
Constant Speed
Source of the Master
02-10
Frequency
Command
Source of the
02-11
Auxiliary Frequency
Command
Combination of the
Master and Auxiliary
02-12
Frequency
Command
Revision July 2008, BE16, SW V4.08 & V5.00
Settings
00: Enable forward/reverse operation
01: Disable reverse operation
02: Disabled forward operation
00: 2-wire: FWD/STOP, REV/STOP
01: 2-wire: FWD/REV, RUN/STOP
02: 3-wire operation
00: Disable. Operation status is not changed
even if operation command source Pr.02-
01 and/or Pr.02-14 is changed.
01: Enable. Operation status is not changed
even if operation command source Pr.02-
01 and/or Pr.02-14 is changed.
02: Disable. Operation status will change if
operation command source Pr.02-01
and/or Pr.02-14 is changed.
03: Enable. Operation status will change if
operation command source Pr.02-01
and/or Pr.02-14 is changed.
00: Decelerate to 0 Hz
01: Coast to stop and display "EF"
02: Continue operation by last frequency
command
00: Based on accel/decel time
01: Constant speed
02: Based on accel/decel time, but frequency
command will be 0 when stopped.
0.01~1.00 Hz/msec
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
00: Master frequency + auxiliary frequency
01: Master frequency - auxiliary frequency
Chapter 5 Parameters|VFD-B Series
Factory
Setting
00
00
00
00
00
0.01
00
00
00
Customer
5-5