Under-Current Detection Restart Delay Time; User-Defined Low-Voltage Detection Level (Lv); User-Defined Low-Voltage Detection Time - Delta VFD-B User Manual

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-B Series
06 - 15

Under-Current Detection Restart Delay Time

Settings
If output current is lower than the setting Pr.06-12 for a time that exceeds Pr.06-13 setting
during operation, the AC drive will warn per Pr.06-14 setting. If Pr.06-14 is set to 03, the AC
drive will restart after the delay time set by Pr.06-15 is up.
06 - 16

User-Defined Low-Voltage Detection Level (Lv)

Settings
06 - 17

User-Defined Low-Voltage Detection Time

Settings
When the DC BUS voltage is lower than the setting of Pr.06-16 for a time exceeding the
setting of Pr.06-17, the AC motor drive will output a signal when Pr.03-00 ~ Pr.03-03 is set to
28.
06 - 18
Reserved
5-70
1~600 min
00 Disabled
230V series: 220 ~ 300VDC
460V series: 440 ~ 600VDC
575V series: 520 ~ 780VDC
0.1~ 3600.0 sec
Factory Setting: 10
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Factory Setting: 0.5
Revision July 2008, BE16, SW V4.08 & V5.00
Unit: 1
Unit: 1
Unit: 0.1