Delta VFD-B User Manual page 68

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Parameter
Explanation
05-22
Time Duration of 6th
Step Speed
05-23
Time Duration of 7th
Step Speed
05-24
Time Duration of 8th
Step Speed
05-25
Time Duration of 9th
Step Speed
05-26
Time Duration of
10th Step Speed
05-27
Time Duration of
11th Step Speed
05-28
Time Duration of
12th Step Speed
05-29
Time Duration of
13th Step Speed
05-30
Time Duration of
14th Step Speed
05-31
Time Duration of
15th Step Speed
05-32
Time Unit Settings
The Amplitude of
05-33
Wobble Vibration
Wobble Skip
05-34
Frequency
Group 6 Protection Parameters
Parameter
Explanation
Over-Voltage Stall
06-00
Prevention
Over-Current Stall
06-01
Prevention during
Accel
Over-Current Stall
06-02
Prevention during
Operation
Over-Torque
06-03
Detection Mode
(OL2)
Revision July 2008, BE16, SW V4.08 & V5.00
Settings
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00 to 65500 sec or 00 to 6550.0 sec
00: 1 sec
01: 0.1 sec
0.00~400.00 Hz
0.00~400.00 Hz
Settings
230V series: 330.0V to 410.0V
460V series: 660.0V to 820.0V
575V series: 825.0V to1025.0V
00: Disable over-voltage stall prevention
20 to 250%
20 to 250%
00: Disabled
01: Enabled during constant speed operation.
After the over-torque is detected, keep
running until OL1 or OL occurs.
02: Enabled during constant speed operation.
After the over-torque is detected, stop
running.
Chapter 5 Parameters|VFD-B Series
Factory
Setting
00
00
00
00
00
00
00
00
00
00
00
0.00
0.00
Factory
Setting
390.0V
780.0V
975.0V
170
170
00
Customer
Customer
5-11