WARNING!
1.
Short-circuiting [B2] or [-] to [+2/B1] can damage the AC motor drive.
Grounding terminals (
Make sure that the leads are connected correctly and the AC drive is properly grounded.
(Ground resistance should not exceed 0.1 Ω .)
Use ground leads that comply with local regulations and keep them as short as possible.
Multiple VFD-B units can be installed in one location. All the units should be grounded
directly to a common ground terminal, as shown in the figure below. Ensure there are no
ground loops.
2.4.4 Control Terminals
Circuit diagram for digital inputs (SINK current 16mA.)
SINK Mode
multi-input
terminal
DCM
Terminal symbols and functions
Terminal
Symbol
FWD
Forward-Stop command
REV
Reverse-Stop command
Revision July 2008, BE16, SW V4.08 & V5.00
)
excellent
+24
Internal Circuit
Terminal Function
Chapter 2 Installation and Wiring|VFD-B Series
not allowed
good
SOURCE Mode
Multi-Input
Terminal
+24V
Internal Circuit
Factory Settings (SINK)
ON: Connect to DCM
ON:
Run in FWD direction
OFF:
Stop acc. to Stop Method
ON:
Run in REV direction
OFF:
Stop acc. to Stop Method
DCM
2-21